Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T10OT00505

Parcel: 13213063A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10OT00505

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2010 FIRE - FINAL Approved
03/18/2010 FIRE - FINAL Denied 1. Need addresses numbers posted on building and unit numbers on doors.
2. Will need dust control system installed in woodworking cabinet shop IFC 1903.2
3. Allowed up to 60 gals total of flammable and combustable liquids in individual containers or portable tank, if over 60 gals then you will need to install an approved cabinet listed under UL-1275.
4. No spray finishing of flammables allowed will need to install an spray booth and sprinkler system for it.
5. No smoking signs shall be posted 1903.5.3
6. All electrical shall be approved type for woodworking cabinet shops. IFC 605
7. Air lines shall be an approved type materials, plastic water pipe not allowed.
8. All extension cords are use as temporary use only and not use used as permanent wiring. All cords shall be in good condition with out damages and grounding type plug