Permit: T10OT00482

Parcel: 12810082B

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
03/17/2010 FIRE - FINAL Approved Approved 3/17/10
03/11/2010 FIRE - FINAL Partial Approval Partial approval 3/11/10
Still need updated floor plans. OK to start business operations.
03/05/2010 FIRE - FINAL Denied Not approved 3/5/10
1.) Need updated floor plans. Must be reviewed and stamped.
2.) Sticky thumb-turn lock on W. front door. Hard to unlock.
3.) Emergency back-up light, east front door. burnt out.
4.) Secure racks in back storage area.
5.) Need directional exit signs and emergency back-up lighting for the back storage area.
6.) Lable the rear 3 center doors, "DOOR BLOCKED". 6 inch high letters minimum .
7.) Replace ceiling tile (with hole) Back storage area by stairs.
8.) Need current annual sprinkler inspection report
9.) Need current 5 year check valve inspection report.