Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT00482
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2010 | FIRE - FINAL | Approved | Approved 3/17/10 | |
03/11/2010 | FIRE - FINAL | Partial Approval | Partial approval 3/11/10 Still need updated floor plans. OK to start business operations. |
|
03/05/2010 | FIRE - FINAL | Denied | Not approved 3/5/10 1.) Need updated floor plans. Must be reviewed and stamped. 2.) Sticky thumb-turn lock on W. front door. Hard to unlock. 3.) Emergency back-up light, east front door. burnt out. 4.) Secure racks in back storage area. 5.) Need directional exit signs and emergency back-up lighting for the back storage area. 6.) Lable the rear 3 center doors, "DOOR BLOCKED". 6 inch high letters minimum . 7.) Replace ceiling tile (with hole) Back storage area by stairs. 8.) Need current annual sprinkler inspection report 9.) Need current 5 year check valve inspection report. |