Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT00471
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2010 | FIRE - FINAL | Approved | Approved 5/12/10 | |
03/23/2010 | FIRE - FINAL | Denied | Not approved 3/23/10 1.) Need an illuminated EXIT sign for the 2nd. required exit door. 2.) Emergency back-up lighting is required for required exits. 3.) Need panic hardware for east exit door. 4.) Exit gate for the enclosed area outside must be readily openiable. 5.) Need accurate and approved floor plans for the building. 6.) Storage of combustible materials under stairway is prohibited. 7.) Need the 6 month inspection report for the hood system. 8.) Need the current annual inspection report for the "K" type and the "A-B-C" type portable fire extinguihers. 9.) Need plans indicating proper fire protection coverage for the cooking appliance under kitchen hood. 10.) All openings on walls and ceilings must be protected from fre and smoke. 11.) Will need approved plans and permit for proposed installment of Deck-Style pizza oven. |