Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2010 | FIRE - FINAL | Approved | ||
| 02/17/2010 | FIRE - FINAL | Denied | 1. Wiring to front lights in conduit. 2. Wiring back of building needs to be in conduit anything below 7' in height or wiring not approved for sunlight use. 3. Cover plate needed for breaker box. 4. Break room cover plate needed on switch and outlet. 5. Egress door back room remove slide bolt locks. 6. Low voltage timer box missing cover plate need to secure box from opening or replace box (by front main door). 7. Replace missing outlet plates in office area. 8. Front empty office switch box needs cover plate. 9. Cover plate on j-box above desk in office needs cover plate. 10. Label front door with the following: "This door to remain unlocked when building is Occupied", 1" high letters on a contrasting background. 12. Install thumb style dead bolt locks on rear egress doors. |