Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT00285
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2010 | FIRE - FINAL | Approved | ||
04/13/2010 | FIRE - FINAL | Denied | Stopped by talked to tenant advised them permit is going to expire so they will need to finish C of O or move all merchandise out. One of the front doors needs to open outward so that requirements for two exits are met. Remove exit sign over one of the front doors that is not the required exit. Remove exit sign over roll up door southwest wall. Install exit sign showing way out to rear exit from sales floor. |
|
02/08/2010 | FIRE - FINAL | Denied | Need fire door or wall up first before C of O approval is given. (Brick wall) Need approved plans and permit before wall is repaired or fire door put in place. Need occupant Load checked building is 4280 square feet dived by 30 is 142 occupant Stamp plans show 20 occupant Load. |