Date Description Inspector Results Comments
02/10/2010 FIRE - FINAL Approved
02/08/2010 FIRE - FINAL Denied NEED YEARLY SPRINKLER INSPECTION DONE LAST ON FILE 1/18/2008.
NEED SPRINKLER COVERAGE IN ELECT. ROOM UNABLE TO ENTER ROOM. IF NO COVERAGE IN ROOM NEED TO ADD COVERAGE, WILL NEED APPROVED PALN AND PERMITS BEFORE WORK IS DONE.
CORRECT BLOCK UPRIGHT HEAD BLOCKED BY COPPER GROUND AND BRACE FOR WALL, CAN NOT BLOCK SPRINKLER FLOW PATTERN.