Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2010 | FIRE - FINAL | Approved | ||
| 01/14/2010 | FIRE - FINAL | Denied | Metal storage shed all wiring shall be in conduit: Outlet to cooler - 6 foot Fluorescent lights hanging Outlets outside under shade covers shall be GFIC protected Behind building electrical box clean up wiring hanging out the bottom. Remove dead brush pile Office/sales building: Outside outlets need to be GFCI protected Can not use plastic water for air lines, need to use approved metal piping for air lines outside driveways all the way back to the compressor. Need to hire a license electrician to install 2 phase vacuum system; you need a permit for this work. Front door bars label them with the following "This Door To Remain Unlocked When Building Is Occupied". 1 inch high letters |