Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10OT00093
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2010 | FIRE - FINAL | Approved | Approved 2/25/10 | |
02/12/2010 | FIRE - FINAL | Denied | Not approved 2/12/10. 1.) Need current. updated and approved floor plans. 2.) Need to provide an emergency back-up light for both required exits. 3.) Exit or path to exit can not pass through a storage area unless 'EXCEPTION REQUIREMENTS" are met. 4.) The main exit is an automatic sliding door. This door must remain in the "automatic open" positon when the store is occupied 5.) Need a sign over the main door "DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED". |
|
01/28/2010 | FIRE - FINAL | Denied | Not approved 1/28/10 1.) Need address numbers for the business. Must be 12 inches high minimum and must be readily visible from street. 2.) Need approved floor plans. 3.) Need emergency back-up lights for both exits. 4.) Required secondary exits can not pass through a storage area unless exception requirements have been met. 5.) Need to keep area around electrical panel clear at all times. |