Permit: T10OT00073

Parcel: 11711085A


Addresses:

65 E PENNINGTON ST

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
07/28/2010 FIRE - FINAL Approved Approved 7/28/10
07/14/2010 FIRE - FINAL Denied Not approved 7/14/10
1.) Need sign over main exit door reading,"DOORMUST REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED"
2.) Need updated and approved floor plans
3.) Only approved adaptors are allowed to be used
4.) extinguishers must be labled
5.) Holes in walls and ceilings must be covered to protect from passage of smoke and fire.
6.) Replace missing civer plates
a.) office room # 3/4
b.) A/C room
7.) Need clear working area in front of electrical panel.
8.) Need breaker blank in electrical panel
9.) Remove double-cylinder lock from the rear door and replace with thumb-turn lock