Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2010 | MECHANICAL - FINAL | Approved | ||
| 04/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNIT DATA PLATE MISSING, UNABLE TO DETERMINE AMPERAGE REQUIREMENTS 2) CONDENSATE TO TERMINATE 6" ABOVE GRADE 3) CONDENSATE TO BE PAINTED TO PROTECT FROM U.V. LIGHT 4) PROVIDE SERVICE RECEPT WITHIN 25' OF UNIT ON ROOF |
|
| 04/16/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ROOF ACCESS |