Permit: T10ME00725

Parcel: 128100810

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00725

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/23/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) USE FULL LENGTH BLOCKS EVERY 4' ON CONDENSATE DRAINS
2) DO NOT STACK BLOCKS, USE REDWOOD OR PRESSURE TREATED WOOD
3) PROVIDE A FULL LENGTH SAMPLING TUBE AND SUPPORT PROPERLY FOR 15 TON UNIT
4) TESTED DUCT SMOKE DETECTORS
01/27/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONDENSATE FROM 7 TON UNIT DOES NOT HAVE ADEQUATE SLOPE
2) DUCT SMOKE DETECTORS MUST HAVE AN AUDIBLE AND VISIBLE ALARM TO ALERT THE TENANT THAT THE DETECTOR IS IN ALARM
3) HOUSE PANEL CANNOT BE IN ANOTHER SPACE
01/11/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A BUSHING WHERE LOW VOLTAGE WIRE ENTERS THE 7 TON UNIT
2) DO NOT TERMINATE CONDENSATE INTO THE ROOF DRAIN FOR 7 TON UNIT
3) RELOCATE DUCT SMOKE DETECTOR TO THE RETURN AIR PLENIUM ON 15 TON UNIT AND PROVIDE AUDIBLE AND VISIBLE ALARM
4) 7 TON UNIT DOES NOT REQUIRE ONE, BUT MANAGEMENT MIGHT WANT TO RE-USE THE EXISTING DETECTOR
5) 15 TON UNIT OVERFUSED-45 AMP IS MAX
12/29/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*