Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/16/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 2) LOW VOLTAGE WIRING MUST BE PRTOTECTED FROM DAMAGE 3) DO NOT HAVE PVC WITHIN 6" OF VENT CONNECTOR. USE COPPER IF NECESSARY 4) CONNECT THE OVERFLOW SENSOR ON PUMP. WHERE IS THE BRUSH FOR THE CONDENSATE TRAP ? 5) NO ACCESS TO ROOF. WHERE IS CONDENSATE TERMINATED ? PROVIDE ACCESS |