Permit: T10ME00697

Parcel: 134171910


Addresses:

7242 E ELI DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/21/2011 MECHANICAL - FINAL Approved STRUCTURAL IS OK FOR EXISTING SPAN EVEN WITHOUT TRUSS CONFIGURATION.
12/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ITEM 3 DATED 12/23/10 STILL NOT CORRECTED, ALL OTHER ITEMS OK
12/23/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AN APPROVED GAS SHUT OFF VALVE AT FURNACE
2) FURNACE VENT CONNECTOR 1ST FITTING NOT CRIMPED OR GOING SAME DIRECTION AS FLOW. PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTION
3) PROVIDE THE REQUIRED STRUCTURAL DRAWING FOR NEW A/C ON THE ROOF
4) PROVIDE PROTECTIVE COATING ON EXPOSED ARMAFLEX
5) SUPPORT ELECTRIC CONDUIT
6) TERMINATE CONDENSATE TO AN APPROVED LOCATION