Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/20/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTION DATED 12-17-10 HAVE NOT BEEN DONE, A RE-FEE WILL BE ATTACHED TO NEXT INSPECTION IDF ALL ITEMS NOT CORRECTED |
|
| 12/17/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) ITEMS DATED 12/14/10 HAVE BEEN CORRECTED 2) DO NOT USE NEUTRAL WIRE AS HOT LEG 3) CONDENSATE NOT PROPERLY TERMINATED |
|
| 12/14/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE ACCESS TO ROOF 2) OLD (ABESTOS ?) FIBER FLUE PIPE IS BROKEN AT CEILING, REMOVE AND REPLACE WITH B-VENT 3) FLUE PIPING NOT PROPERLY INSTALLED, PROVIDE TIGHT FITTING JOINTS. DO NOT USE PLUMBERS TAPE TO SUPPORT FLUE PIPING |