Permit: T10ME00625

Parcel: 123022610


Addresses:

2628 E LINDEN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/16/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/02/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE GFI PROTECTED SERVICE OUTLET ON ROOF WITHIN 25' OF UNIT. DO NOT PULL POWER FROM CONDENSATE UNIT
2) PROVIDE GROUND WIRES TO CONDENSER (WHITE IS NEUTRAL, GREEN IS GROUND)
3) PROVIDE ROOF JACK ON ELECTRIC PENETRATIONS THRU ROOF
4) SEAL DUCT IN MECH ROOM INSULATE DUCT IN MECH ROOM
5) HORIZONTAL FLUE PIPE NOT TO EXCEED 60 DEGREE
6) PROVIDE SECONDARY DRAIN ON EVAP COIL. (EZ-TRAP)
7) POWER CORD TO BE MIN. 6" AWAY FROM FLUE PIPE
10/26/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LADDER TO ACCESS ROOF
2) PROVIDE ALL REQUIRED DOCUMENTS