Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/07/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL WALL AMERIVENT TEE IS NOT COMPATABLE WITH DURA VENT DBL WALL VENT PIPE. DO NOT USE A DBL WALL TEE 2) USE A SINGLE WALL TEE AND CONNECT WITH SINGLE WALL FITTINGS. DO NOT USE FOIL TAPE 3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX |