Permit: T10ME00598

Parcel: 133325020


Addresses:

9011 E 9TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/08/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/01/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE ALL DUCT TAPE USED OUTDOORS ON LINE SET
2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
3) PROVIDE PLUGS IN OPEN KNOCKOUTS IN ELECTRIC DISCONNECT
4) ID FUSE SLEEVE ON FAN COIL AND SEAL ALL CONNECTIONS
5) 15 AMP FUSES NOT ADEQUATE IF USING A HEAT STRIP
6) PLUG ABANDONED GAS LINE TO OLD FURNACE