Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/01/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL DUCT TAPE USED OUTDOORS ON LINE SET 2) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 3) PROVIDE PLUGS IN OPEN KNOCKOUTS IN ELECTRIC DISCONNECT 4) ID FUSE SLEEVE ON FAN COIL AND SEAL ALL CONNECTIONS 5) 15 AMP FUSES NOT ADEQUATE IF USING A HEAT STRIP 6) PLUG ABANDONED GAS LINE TO OLD FURNACE |