Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/28/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC MUST HAVE MINIMUM 6" CLEARANCE FROM FURNACE VENT CONNECTOR. PROVIDE A STAND PIPE IN CONDENSATE VENT HIGHER THAN DRAIN PAN OR CAP OFF VENT 2) PROVIDE A SEDIEMENT TRAP IN GAS LINE AT FURNACE 3) BLOCK AND CLAMP ELECTRIC CONDUIT ON ROOF 4) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT 5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF |