Permit: T10ME00587

Parcel: 138130220


Addresses:

401 W CALLE RAMONA

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/03/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/28/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PVC MUST HAVE MINIMUM 6" CLEARANCE FROM FURNACE VENT CONNECTOR. PROVIDE A STAND PIPE IN CONDENSATE VENT HIGHER THAN DRAIN PAN OR CAP OFF VENT
2) PROVIDE A SEDIEMENT TRAP IN GAS LINE AT FURNACE
3) BLOCK AND CLAMP ELECTRIC CONDUIT ON ROOF
4) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF