Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 02/28/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTEND VENT IN CONDENSATE DRAIN HIGHER THAN DRAIN PAN 2) PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE 3) PROVIDE 40 AMP FUSES AND A 40 AMP BREAKER FOR CONDENSOR 4) USE ONLY A CUTLER HAMMER BREAKER 5) SEAL THE HOLE IN THE WALL WHERE REFER LINES PENETRATE 6) INSTALL SCREWS IN METAL COVERING AT CONDENSOR |