Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 11/18/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/17/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT INCREASER TO BE INSTALLED DIRECTLY ONTO THE FURANCE OUTLET. BE SURE ALL CRIMPED ENDS ARE SAME DIRECTION AS AIR FLOW 2) DO NOT HAVE PVC WITHIN 6" OF SINGLE WALL VENT CONNECTOR 3) ZIP TIES ARE RESTRICTING WATER FLOW THRU PLASTIC PUMP HOSE 4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 5) USE AN OUTDOOR EMT FITTING AT CONNECTION TO SERVICE RECEPT |