Permit: T10ME00547

Parcel: 140140370


Addresses:

5425 S GREENWAY DR

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE CANNOT TERMINATE AT WASTE VENT, PIPE TO WITHIN 6" OF GRADE. DO NOT DUMP ON ANY HARD SURFACES
08/26/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO FILTER
2) PROVIDE SECONDARY DRAIN OF SENSOR
3) ALL PVC JOINTS ARE TO BE PRIMED, ALL PRIMER IS TO BE PURPLE IN COLOR PER UPC
4) SECURE LOW VOLTAGE WIRING CLAMP AND TIGHTEN
5) PROVIDE P-TRAP AT CONDENSATE DRAIN
6) DO NOT CUT PLUG END OFF OF COND. PUMP
7) PROVIDE APPROVED ACCESS OF CORD INTO CABINET
8) UNIT OVERFUSED
9) PROVIDE SERVICE OUTLET ON ROOF
10) CONDENSATE NOT PROPERLY TERMINATED