Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE CANNOT TERMINATE AT WASTE VENT, PIPE TO WITHIN 6" OF GRADE. DO NOT DUMP ON ANY HARD SURFACES |
|
| 08/26/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ACCESS TO FILTER 2) PROVIDE SECONDARY DRAIN OF SENSOR 3) ALL PVC JOINTS ARE TO BE PRIMED, ALL PRIMER IS TO BE PURPLE IN COLOR PER UPC 4) SECURE LOW VOLTAGE WIRING CLAMP AND TIGHTEN 5) PROVIDE P-TRAP AT CONDENSATE DRAIN 6) DO NOT CUT PLUG END OFF OF COND. PUMP 7) PROVIDE APPROVED ACCESS OF CORD INTO CABINET 8) UNIT OVERFUSED 9) PROVIDE SERVICE OUTLET ON ROOF 10) CONDENSATE NOT PROPERLY TERMINATED |