Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/24/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL THE 3" INCREASER FOR VENTING DIRECTLY ON THE FURNACE FLUE OUTLET AS PER INSTALL INSTRUCTIONS 2) RUN SINGLE WALL VENT CONNECTOR INTO THE DBL WALL VENT AT THE CEILING 3) EVERYTHING ELSE IS OK |
|
| 08/31/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU CANNOT USE PIPE DOPE TO FASTEN PVC FITTINGS. PROVIDE PURPLE PRIMER ON ALL GLUED FITTINGS PRIOR TO GLUE 2) FURNACE VENT CONNECTOR NOT INSTALLED CORRECTLY 3) INSULATE SHEET METAL SLEEVE ABOVE EVAP COIL 4) 3/8" ID X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU 5) PAINT EXPOSED PVC WITH LATEX PAINT AND PROVIDE SUPPORT 6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 7) LOW VOLTAGE WIRE MUST BE PROTECTED FROM DAMAGE 8) DO NOT USE WHITE CONDUCTORS TO POWER THE A/C UNIT 9) TAPE ALL ENDS WITH BLACK TAPE |