Permit: T10ME00535

Parcel: 133130300


Addresses:

7801 E ELIDA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/01/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
09/24/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL THE 3" INCREASER FOR VENTING DIRECTLY ON THE FURNACE FLUE OUTLET AS PER INSTALL INSTRUCTIONS
2) RUN SINGLE WALL VENT CONNECTOR INTO THE DBL WALL VENT AT THE CEILING
3) EVERYTHING ELSE IS OK
08/31/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU CANNOT USE PIPE DOPE TO FASTEN PVC FITTINGS. PROVIDE PURPLE PRIMER ON ALL GLUED FITTINGS PRIOR TO GLUE
2) FURNACE VENT CONNECTOR NOT INSTALLED CORRECTLY
3) INSULATE SHEET METAL SLEEVE ABOVE EVAP COIL
4) 3/8" ID X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU
5) PAINT EXPOSED PVC WITH LATEX PAINT AND PROVIDE SUPPORT
6) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
7) LOW VOLTAGE WIRE MUST BE PROTECTED FROM DAMAGE
8) DO NOT USE WHITE CONDUCTORS TO POWER THE A/C UNIT
9) TAPE ALL ENDS WITH BLACK TAPE