Permit: T10ME00530

Parcel: 133280130


Addresses:

8441 E 3RD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/01/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
08/17/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
2) PROVIDE HOSE CLAMPS AT PLASTIC HOSE CONNECTIONS
3) PROVIDE A PERMIT FOR THE NEW ELECTRIC SUB PANEL
4) #12 WIRE NOT ADEQUATE FOR 30 AMP WATER HEATER BREAKER
5) REMOVE ALL DUCT TAPE USED OUTDOORS AND PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
6) PROVIDE A GFI SERVICE RECEPT
7) ISOLATE COPPER LINES FROM STEEL STRAPS
8) DISCONNECT WIRED BACKWARDS
9) SECURE ELECTRIC CONDUIT AT CONDENSOR WITH OTHER MEANS THEN TAPE
10) UV RATED ZIP TIES ARE OK