Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 08/17/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 2) PROVIDE HOSE CLAMPS AT PLASTIC HOSE CONNECTIONS 3) PROVIDE A PERMIT FOR THE NEW ELECTRIC SUB PANEL 4) #12 WIRE NOT ADEQUATE FOR 30 AMP WATER HEATER BREAKER 5) REMOVE ALL DUCT TAPE USED OUTDOORS AND PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX 6) PROVIDE A GFI SERVICE RECEPT 7) ISOLATE COPPER LINES FROM STEEL STRAPS 8) DISCONNECT WIRED BACKWARDS 9) SECURE ELECTRIC CONDUIT AT CONDENSOR WITH OTHER MEANS THEN TAPE 10) UV RATED ZIP TIES ARE OK |