Permit: T10ME00522

Parcel: 135104210

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/05/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/21/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET
2) REMOVE ALL FOIL TAPE AND PROVIDE MINIMUM 3 SCREWS IN EACH JOINT OF FURNACE VENT CONNECTOR. JOINTS NEED TO FIT BETTER
3) INSULATE BARE SHEET METAL DUCTING IN FURNACE CLOSET
4) PROVIDE SEDIMENT TRAP IN GAS LINE AT FURNACE CONNECTION
5) REPLACE DETERIORATED ARMAFLEX AT CONDENSOR AND PROVIDE A PROTECTIVE COATING
6) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. OK TO TERMINATE INTO RAIN GUTTER. SUPPORT COPPER LINE EVERY 6'