Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 09/21/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET 2) REMOVE ALL FOIL TAPE AND PROVIDE MINIMUM 3 SCREWS IN EACH JOINT OF FURNACE VENT CONNECTOR. JOINTS NEED TO FIT BETTER 3) INSULATE BARE SHEET METAL DUCTING IN FURNACE CLOSET 4) PROVIDE SEDIMENT TRAP IN GAS LINE AT FURNACE CONNECTION 5) REPLACE DETERIORATED ARMAFLEX AT CONDENSOR AND PROVIDE A PROTECTIVE COATING 6) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. OK TO TERMINATE INTO RAIN GUTTER. SUPPORT COPPER LINE EVERY 6' |