Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) INSULATE BARE SHEET METAL DUCTS IN CLOSET 2) EXTEND VENT ON CONDENSATE DRAIN ABOVE DRAIN PAN 3) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 4) SUPPORT COPPER DRAIN LINE ON ROOF AT 6' INTERVALS |