2025 N JENNIFER AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00496

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/09/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WHEN A SECONDARY OUTLET IS PROVIDED IN THE COIL, YOU MUST USE THIS OUTLET FOR THE OVERFLOW SENSOR
2) DO NOT PUT OVERFLOW SENSOR IN THE PRIMARY DRAIN LINE
3) EXTEND VENT ON PRIMARY DRAIN ABOVE DRAIN PAN IN COIL
08/26/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN OVERFLOW SENSOR IN SECONDARY DRAIN OUTLET
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) 3/8" ID X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE
4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX