Permit: T10ME00488

Parcel: 116131050

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/17/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/18/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL PVC IS TO BE PRIMERED AT ALL JOINTS AND PRIMER IS TO BE PURPLE IN COLOR
2) SCREWS ON FLUE PIPING JOINTS ARE NOT PROPERLY DISPERSED
3) CRIMPED END OF FLUE PIPING IS TO FIT A MINIMUM OF 1" INTO RECEVING END (CRIMPED AREA SHOULD NOT BE EXPOSED)
4) PROVIDE APPROVED COATING ON OUTDOOR LINE SETS, MIL TAPE NOT APPROVED FOR U.V. RATING
5) PROVIDE SERVICE OUTLET WITHIN 25' OF OUTDOOR UNIT
6) UNIT OUT DOR IS OVER FUSED
7) BLACK WIRE NOT TO BE USED AS GROUND