Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/26/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL TAPE FROM FLUE PIPING 2) PROVIDE PROPER, TIGHT FITTING JOINTS ON FLUE PIPING 3) PROVIDE A MIN. 3 SCREWS ON ALL SINGLE WALL FLUE JOINTS, SCREWS ARE TO BE EVENLY SPACED 4) FLUE PIPE TO WATER HEATER INSTALLED BACKWARDS 5) CONDENSATE ON EXTERIOR IS TO BE STRAPPED TO BLDG OR SLAB, PVC TO BE COATED (PAINTED) 6) PIPE INSULATION ON EXTERIOR CONDENSOR TO BE PROPERLY COATED (MILL TAPE NOT APPROVED FOR EXTERIOR USE) |
|
| 10/15/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE HOME |