Permit: T10ME00482

Parcel: 136235150


Addresses:

3632 S QUEBEC PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/30/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PVC CANNOT BE WITHIN 6" OF A SINGLE WALL VENT CONNECTOR
2) USE COPPER DRAIN LINE
3) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX
5) SUPPORT COPPER DRAIN LINE ON ROOF EVERY 6'