Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/30/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC CANNOT BE WITHIN 6" OF A SINGLE WALL VENT CONNECTOR 2) USE COPPER DRAIN LINE 3) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 5) SUPPORT COPPER DRAIN LINE ON ROOF EVERY 6' |