Permit: T10ME00479

Parcel: 136010090

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00479

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/11/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) IS THERE A HEAT STRIP INSTALLED ? IF NOT THEN CIRCUIT BREAKER EXCEEDS MAX. OVER CURRENT
2) I.D. CIRCUIT BREAKER. IF THERE IS A HEAT STRIP THEN INDICATE ON DATA PLATE AND FUSE ACCORDINGLY
3) NEED ACCESS TO ALL DUCT UNDER THE HOME
4) BE SURE ALL DUCT IS MINIMUM 4" ABOVE THE DIRT
5) ALL INSULATION ON DUCT TO BE MINIMUM R8