Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/11/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IS THERE A HEAT STRIP INSTALLED ? IF NOT THEN CIRCUIT BREAKER EXCEEDS MAX. OVER CURRENT 2) I.D. CIRCUIT BREAKER. IF THERE IS A HEAT STRIP THEN INDICATE ON DATA PLATE AND FUSE ACCORDINGLY 3) NEED ACCESS TO ALL DUCT UNDER THE HOME 4) BE SURE ALL DUCT IS MINIMUM 4" ABOVE THE DIRT 5) ALL INSULATION ON DUCT TO BE MINIMUM R8 |