Permit: T10ME00478

Parcel: 136287040

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/17/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
04/29/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/04/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU CANNOT USE 1 LEG FROM THE 240 VOLT AIR CONDITIONING CIRCUIT TO POWER A SERVICE RECEPT
2) YOU CANNOT USE THE GROUND BAR FROM THE DISCONNECT FOR NEUTRAL
3) PROVIDE A DEDICATED CIRCUIT FROM THE PANEL FOR THE SERVICE RECEPT
4) I.D. CIRCUIT BREAKER FOR THE CONDENSOR AND SERVICE RECEPT
5) SERVICE RECEPT BREAKER NOT TO EXCEED 20 AMP
12/03/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSULATE SHEET METAL SLEEVE ON FAN COIL
2) MAKE UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED
3) USE THE CORRECT FITTING AT ELECTRICAL CONNECTION TO FAN COIL
4) PROVIDE A ROOF JACK AT CONDENSATE PENETRATION THRU ROOF
5) A/C DISCONNECT OVER FUSED. ID A/C AND SERVICE RECEPT CIRCUIT BREAKERS