Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CONFIRMED ROOF TOP DRAWING |
|
| 12/08/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE THE REQUIRED ROOF TOP DRAWING APPROVED BY CITY OF TUCSON |
|
| 10/14/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A PROTECTIVE COVER OVER CANVAS CONNECTOR 2. PROVIDE MIN 1/8" PER FT SLOPE ON ALL SECTION OF CONDENSATE PIPING 3. DO NOT CONNECT NEUTRAL WIRE TO GROUND BAR IN DISCONNECT. REMOVE + WIRE NUT TOGETHER 4. PROVIDE THE REQUIRED ROOF TOP DRAWING FOR NEW A/C |