Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL FOIL TAPE FROM VENT CONNECTOR AND PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS 2) PLASTIC OVERFLOW SENSOR TO CLOSE TO SINGLE WALL VENT. USE COPPER TO 6" AWAY FROM VENT, THEN INSTALL SENSOR 3) WHERE IS DAMPER TO STOP EVAP COOLER FROM BLOWING THRU THE FURNACE ? BAROMETRIC DAMPER REQUIRE ACCESS 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT. J-BOX FOR RECEPT IS BLOCKING REMOVAL OF PANEL COVER |