Permit: T10ME00395

Parcel: 115020300


Addresses:

342 E WAVERLY ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/19/2011 MECHANICAL - FINAL Approved APPROVED PER M. RAMBER DUE TO ITEM #6 FROM 07/22/10 BEING CORRECTED
07/22/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) ALL ITEMS EXCEPT #6 HAVE BEEN CORRECTED
07/07/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ALL ROOF TOP DUCT WITHIN 2" LINER (R-8)
2) PROVIDE PURPLE PRIMER AT ALL PVC JOINTS
3) ALL PVC TO BE COATED THAT IS EXPOSED TO DAYLIGHT
4) ALL CONDENSATE TO TERMINATE AT AN APPROVED LOCATION
5) PROVIDE CITY APPROVED ROOF LOAD CALC
6) UNIT DATA PLATE NOT IDENTIFIED
7) DISCONNECT PULL OUTS NOT LABELED