Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/07/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/18/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. MIL TAPE (PUC PIPE WRAP) NOT APPROVED METHOD FOR COATING PIPE, PROVIDE U.V. RATED LINE SET TAPE OR MANUFACTURERS RECOMMENDED COATING.
2. ALL OTHER ITEMS DATED 10/1/10 HAVE BEEN CORRECTED.
11/15/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE HOME
10/01/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SERVICE OUTLET AT OUT DOOR UNIT
2) ALL OUT DOOR PIPE INSULATION EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE U.V. PROTECTION. DO NOT USE DUCT TAPE
3) UNIT IS OVER FUSED
4) NO EXPOSED ROMEX ALLOWED GROUND WIRE TO ROMEX CUT NOT CONNECTED
5) NO GROUND TO ELECTRICAL PANEL. BREAKERS NOT LABELED
09/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) RE-SCHEDULE-NOT READY