Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/18/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. MIL TAPE (PUC PIPE WRAP) NOT APPROVED METHOD FOR COATING PIPE, PROVIDE U.V. RATED LINE SET TAPE OR MANUFACTURERS RECOMMENDED COATING. 2. ALL OTHER ITEMS DATED 10/1/10 HAVE BEEN CORRECTED. |
|
| 11/15/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME |
|
| 10/01/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SERVICE OUTLET AT OUT DOOR UNIT 2) ALL OUT DOOR PIPE INSULATION EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE U.V. PROTECTION. DO NOT USE DUCT TAPE 3) UNIT IS OVER FUSED 4) NO EXPOSED ROMEX ALLOWED GROUND WIRE TO ROMEX CUT NOT CONNECTED 5) NO GROUND TO ELECTRICAL PANEL. BREAKERS NOT LABELED |
|
| 09/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) RE-SCHEDULE-NOT READY |