Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T10ME00380

Parcel: 113010060


Addresses:

1650 E ROGER RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/19/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/08/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLUE VENTING TO BE 10' AWAY OR 2' ABOVE ANY AIR INTAKE
2) TERMINATE CONDENSATE AT AN APPROVED LOCATION
3) PROVIDE GFI SERVICE OUTLET WITHIN 25' OF SERVICEABLE EQUIPMENT ON ROOF ( OUTLET TO BE AT SAME LEVELS AS UNIT AND HAVE WATER TIGHT COVER)
4) PROIDE #10 MIN. WIRINGTO C.U. #12 ONLY GOOD UP TO 25 AMPS PER TABLE 310.15 NEC
5) PROVIDE RUBBER ISOLATORS ? COPPER LINE SETS ENTER A/C COIL
6) PROVIDE GROUNDED EXTENSION CORD ON CONDENSATE PUMP
7) GROUND PIN HAS BEEN PULLED OUT OF CONDENSATE PUMP ELECTRIC CORD. PUMP NEEDS TO BE REPLACED