Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLUE VENTING TO BE 10' AWAY OR 2' ABOVE ANY AIR INTAKE 2) TERMINATE CONDENSATE AT AN APPROVED LOCATION 3) PROVIDE GFI SERVICE OUTLET WITHIN 25' OF SERVICEABLE EQUIPMENT ON ROOF ( OUTLET TO BE AT SAME LEVELS AS UNIT AND HAVE WATER TIGHT COVER) 4) PROIDE #10 MIN. WIRINGTO C.U. #12 ONLY GOOD UP TO 25 AMPS PER TABLE 310.15 NEC 5) PROVIDE RUBBER ISOLATORS ? COPPER LINE SETS ENTER A/C COIL 6) PROVIDE GROUNDED EXTENSION CORD ON CONDENSATE PUMP 7) GROUND PIN HAS BEEN PULLED OUT OF CONDENSATE PUMP ELECTRIC CORD. PUMP NEEDS TO BE REPLACED |