Permit: T10ME00367

Parcel: 133222510


Addresses:

6851 E FLAMENCO DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
09/08/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE THE REQUIRED ROOF DRAWING FOR NEW A/C
2) PROVIDE A ROOF JACK AT CONDENSATE PENETRATION
3) SERVICE RECEPT CANNOT BE CONNECTED TO A SWITCH IN THE HOUSE
08/17/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) OK FOR FINAL
2) AIR BALANCE OK
08/16/2010 MECHANICAL - FINAL Cancelled IVRS - RI canceled
07/02/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE CAP ON ABANDONED VENT IN FURNACE CLOSET WITH SCREWS
2) 3/8" ID X 24" GAS FLEX NOT ADEQUATE FOR 115,000 BTU
3) DISCONNECT IS WIRED BACKWARDS, LINE AND LOAD ARE SWITCHED. WHITE WIRE NOT ALLOWED
4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
5) PROVIDE THE REQUIRED DRAWING FOR A NEW ROOF TOP INSTALLATION
6) USE PURPLE PRIMER ON ALL PVC JOINTS, BLOCK AND CLAMP PVC EVERY 4', PAINT WITH LATEX PAINT
7) PROVIDE MINIMUM R8 DUCT LINER IN EXPOSED DUCT ON ROOF