Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |
|
| 07/22/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/17/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL PVC JOINTS ARE TO HAVE PRIMER APPLIED PRIOR TO GLUE, PRIMER IS TO BE PURPLE IN COLOR 2) ALL PVC EXPOSED TO U.V. LIGHT IS TO BE COATED WITH LATEX PAINT OR OTHER U.V. RESISTIVE COATING 3) CONDENSATE MAY NOT TERMINATE AT WASTE VENTS TERMINATE AT AN APPROVED LOCATION 4) BLOCKING FOR 3/4" P.V.C. PIPING NOT TO EXCEED 4' 5) ALL DUCT EXPOSED TO EXTERIOR IS TO HAVE MIN R-8 INSULATION (2") 6) PROVIDE SERVICE OUTLET WITHIN 25' AND AT SAME LEVEL AS UNIT. OUTLET TO BE GFI PROTECTED WITH WATER PROOF ENCLOSURE |