Permit: T10ME00364

Parcel: 117190110


Addresses:

423 S ELIAS AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00364

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/06/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ROOF JACK WHERE ELECTRIC CONDUIT PENETRATES ROOF
2) SERVICE OUTLET ON ROOF NOT ACCESSIBLE
3) CONDENSATE DOWN WALL IS TO BE COATED
4) REMOVE THREADS FROM END OF CONDENSATE PIPE
5) PROVIDE ROOF LOAD CALC FOR NEW UNIT ON ROOF
6) RE-ROUTE SEAL TITE FROM DISCONNECT BOX TO UNIT, FLUE IS MELTING SEAL TITE
7) UNIT IS OVER FUSED PROVIDE PROPER SIZE FUSES