Permit: T10ME00347

Parcel: 118036930


Addresses:

2614 W WINDSTAR PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/10/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/10/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE TIGHT FITTINGS AT FLUE PIPE, CRIMP SHOULD NOT BE SHOWING, REPLACE PIPE AS NEEDED
2) ALL ITEMS DATED 7/2/10 HAVE BEEN CORRECTED
11/17/2010 MECHANICAL - FINAL Cancelled CANCELLED PER HOMEOWNER PABLO GARCIA #837-3066
11/17/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
07/02/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN OVERFLOW SENSOR
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) DO NOT HAVE PVC ON PLASTIC HOSE WITHIN 6" OF VENT CONNECTOR
4) REMOVE ALL FOIL TAPE FROM FURNACE VENT AQND PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS DO NOT RE-TAPE
5) HORIZONTAL SECTION OF DBL WALL VENT CANNOT BE MORE THAN 75 PERCENT OF TOTAL HEIGHT
6) DO NOT USE PLUMBERS TAPE TO SECURE THE VENT, USE THE BRACKETS THAT ARE LISTED FOR SUPPORT
7) CONDENSOR OVERFUSED