Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/10/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE TIGHT FITTINGS AT FLUE PIPE, CRIMP SHOULD NOT BE SHOWING, REPLACE PIPE AS NEEDED 2) ALL ITEMS DATED 7/2/10 HAVE BEEN CORRECTED |
|
| 11/17/2010 | MECHANICAL - FINAL | Cancelled | CANCELLED PER HOMEOWNER PABLO GARCIA #837-3066 | |
| 11/17/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/02/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) DO NOT HAVE PVC ON PLASTIC HOSE WITHIN 6" OF VENT CONNECTOR 4) REMOVE ALL FOIL TAPE FROM FURNACE VENT AQND PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS DO NOT RE-TAPE 5) HORIZONTAL SECTION OF DBL WALL VENT CANNOT BE MORE THAN 75 PERCENT OF TOTAL HEIGHT 6) DO NOT USE PLUMBERS TAPE TO SECURE THE VENT, USE THE BRACKETS THAT ARE LISTED FOR SUPPORT 7) CONDENSOR OVERFUSED |