Permit: T10ME00345

Parcel: 128100810

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00345

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
07/06/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 1/8" PER FT SLOPE ON CONDENSATE DRAIN LINE
2) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT
3) SEE BILL FROM LARSON BAKER FOR LOCATION