Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 07/15/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
| 06/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SECONDARY DRAIN ON EVAP COIL 2) CONDENSOR IS OVERFUSED PROVIDE 40 AMP BREAKER 3) PROVIDE SERVICE OUTLET WITHIN 25' OF OUTDOOR UNIT 4) REMOVE DEBRIS FROM COND. DRAIN 5) COAT LINE SETS OUT DOORS WITH U.V. RATED COATINGS |