Permit: T10ME00334

Parcel: 136416450


Addresses:

10041 E MARY DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/21/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
07/15/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY CONTRACTOR
06/08/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SECONDARY DRAIN ON EVAP COIL
2) CONDENSOR IS OVERFUSED PROVIDE 40 AMP BREAKER
3) PROVIDE SERVICE OUTLET WITHIN 25' OF OUTDOOR UNIT
4) REMOVE DEBRIS FROM COND. DRAIN
5) COAT LINE SETS OUT DOORS WITH U.V. RATED COATINGS