Permit: T10ME00320

Parcel: 113031450


Addresses:

742 E MCMILLAN DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/29/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/09/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPER CLEARANCE TO COMBUSTIBLES
2) PROVIDE SECONDARY DRAIN AT COIL
3) TERMINATE CONDENSATE IN AN APPROVED MANNER
4) COAT ALL FOAM PIPE INSULATION EXPOSED TO U.V.
5) PROVIDE APPROVED SERVICE OUTLET WITHIN 25' OF R.T.U.