Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/20/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PVC TO CLOSE TO VENT CONNECTOR, USE COPPER IF NECESSARY AND 6" CLEARANCE IS REQUIRED
2) SECURE PUMP DRAIN LINE IN CLOSET
3) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE. CONDENSATE TO TERMINATE TO WITHIN 6" OF GROUND. TERMINATE COPPER INTO PVC WITH A FITTING. PAINT EXPOSED PVC WITH LATEX PAINT
4) PROVIDE A PROTECTIVE COATING ON ALL EXPOSED ARMAFLEX
5) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
6) PROVIDE A ROOF JACK AT ELECTRIC PENETRATION THRU ROOF
7) SEAL SCREW HOLES AT DISCONNECT MOUNT
8) USE ONLY A SQUARE D BREAKER IN PANEL FOR A/C