Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE TO TERMINATE AT AN APPROVED LOCATION 2) ALL PVC JOINTS ARE TO BE PRIMED WITH PURPLE PRIMER PRIOR TO GLUE 3) ALL PVC EXPOSED TO EXTERIOR IS TO BE U.V. COATED (PROTECTED) 4) GAS FLEX NOT TO BE RE-USED PER MANUFACTURE 5) T-STAT WIRE NOT INSTALLED IN AN APPROVED MANNER, MUST BE RUN IN CONDUIT 6) PROVIDE SERVICE DISCONNECT ON ROOF PROPERLY RATED FOR UNIT 7) PROVIDE APPROVED MEANS OF SUPPORT, UNIT NEEDS TO SPAN MIN. 3 TRUSSES (FEET NOT ACCEPTABLE) 8) PROVIDE SEDIMENT TRAP ON GAS PIPING TO UNIT 9) PROVIDE P-TRAP AT CONDENSATE DRAIN 10) ALL ELECTRIC FITTINGS ON ROOF TO BE APPROVED FOR OUTDOOR USE 11) STAND CANNOT BLOCK ACCESS DOORS |
|
| 06/04/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALLED AND LEFT MESSAGE, NO ANSWER, NO CALL BACK. THIS IS SECOND ATTEMPTED TO DO THIS INSPECTION, ANY OTHER FAILURE WILL RESULT IN REFEE |
|
| 05/26/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE ROOF ACCESS |