Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 05/10/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A CHASE NIPPLE OR BUSHING IN THE ELECTRIC DISCONNECT TO PROTECT THE CONDUCTORS PASSING THRU THE CABINET OF THE A/C UNITS 2) THERE IS NO POWER TO THE RECEPT ON THE ROOF AND MUST BE A GFI RECEPT |
|
| 04/28/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL THE SEAM ON ARMAFLEX ON ROOF AND PROVIDE A PROTECTIVE COATING 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 4) DO NOT USE WHITE WIRE FOR POWER TO A/C UNIT. PROVIDE A BUSHING IN ELECTRIC DISCONNECT 5) PROVIDE AN OVERFLOW SENSOR 6) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE |