Permit: T10ME00238

Parcel: 136203320


Addresses:

8243 E ESCALANTE RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/20/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
05/10/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A CHASE NIPPLE OR BUSHING IN THE ELECTRIC DISCONNECT TO PROTECT THE CONDUCTORS PASSING THRU THE CABINET OF THE A/C UNITS
2) THERE IS NO POWER TO THE RECEPT ON THE ROOF AND MUST BE A GFI RECEPT
04/28/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL THE SEAM ON ARMAFLEX ON ROOF AND PROVIDE A PROTECTIVE COATING
2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
3) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF
4) DO NOT USE WHITE WIRE FOR POWER TO A/C UNIT. PROVIDE A BUSHING IN ELECTRIC DISCONNECT
5) PROVIDE AN OVERFLOW SENSOR
6) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE