Permit: T10ME00230

Parcel: 114470020


Addresses:

2621 N ESSEL DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/24/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/27/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE DRAIN MUST SLOPE ENTIRELY DOWNHILL WITH NO RISERS IN THE LINE
2) PAINT EXPOSED PVC WITH LATEX PAINT AS NOTED ON PREVIOUS INSPECTION
3) THE 5 KW HEAT STRIP MUST BE ON A SEPERATE OVERCURRENT PROTECTION DEVICE
4) THE 50 AMP CIRCUIT IS ONLY ENOUGH FOR THE A/C UNIT WITHOUT A HEAT STRIP
5) HEAT STRIP WIRES ARE SHORTED OUTSIDE UNIT
04/29/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DO NOT TERMINATE CONDENSATE TO A SEWER VENT
2) PAINT EXPOSED PVC WITH LATEX PAINT, SUPPORT VENT 4'
3) ELECTRIC DISCONNECT IS OVERFUSED
4) THE 5 KW HEAT STRIP REQUIRED A SEPERATE POWER SUPPLY FUSED AT 30 AMP