Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE DRAIN MUST SLOPE ENTIRELY DOWNHILL WITH NO RISERS IN THE LINE 2) PAINT EXPOSED PVC WITH LATEX PAINT AS NOTED ON PREVIOUS INSPECTION 3) THE 5 KW HEAT STRIP MUST BE ON A SEPERATE OVERCURRENT PROTECTION DEVICE 4) THE 50 AMP CIRCUIT IS ONLY ENOUGH FOR THE A/C UNIT WITHOUT A HEAT STRIP 5) HEAT STRIP WIRES ARE SHORTED OUTSIDE UNIT |
|
| 04/29/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT TERMINATE CONDENSATE TO A SEWER VENT 2) PAINT EXPOSED PVC WITH LATEX PAINT, SUPPORT VENT 4' 3) ELECTRIC DISCONNECT IS OVERFUSED 4) THE 5 KW HEAT STRIP REQUIRED A SEPERATE POWER SUPPLY FUSED AT 30 AMP |