Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 05/06/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE RESCHEDULE YOUR INSPECTION WHEN SOMEONE WILL BE HOME |
|
| 04/29/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DO NOT HAVE A VENT UPSTREAM OF THE CONDENSATE TRAP 2) SEAL ALL CUT SEAMS ON ARMAFLEX 3) 3/8" X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU 4) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. SEE MANUFACTURES INSTRUCTIONS |