04/23/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 3/8" I.D. GAS FLEX IS NOT ADEQUATE FOR 115,000 BTU
2) 1/2" GAS PIPE NOT ADEQUATE IF MORE THAN 20' OF DEVELOPED LENGTH FROM THE GAS METER
3) SERVICE RECEPT ON ROOF NOT ENERGIZED