Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10ME00174
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ITEM 3 DATED 04-12-10 NOT CORRECTED |
|
| 04/12/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROOF TOP DISCONNECT AT A/C UNIT 2) T-STAT WIRE IS TO BE IN CONDUIT 3) PROVIDE SERVICE OUTLET WITHIN 25' OF EQUIPMENT ON ROOF (GFI WITH WATER TIGHT COVER) 4) PROVIDE SEDIMENT TRAP AT GAS INLET TO UNIT ON ROOF 5) COAT PVC PIPE ON ROOF AND ALL EXTERIOR WITH PAINT |