Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ITEM 3 DATED 04-12-10 NOT CORRECTED |
|
| 04/12/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROOF TOP DISCONNECT AT A/C UNIT 2) T-STAT WIRE IS TO BE IN CONDUIT 3) PROVIDE SERVICE OUTLET WITHIN 25' OF EQUIPMENT ON ROOF (GFI WITH WATER TIGHT COVER) 4) PROVIDE SEDIMENT TRAP AT GAS INLET TO UNIT ON ROOF 5) COAT PVC PIPE ON ROOF AND ALL EXTERIOR WITH PAINT |